Analog input
(AI) module
|
|
 |
Voltage
input |
Current
input |
| Number
of input point |
6
points / 14-bit |
| Digital
input value |
-8192
~ +8191 or 0 ~ 16383 |
| Input
signal range |
Bipolar |
-10
~ 10V or -5 ~ 5V
|
-20
~ 20mA or 10 ~ 10mA |
| Unipolar |
0
~ 10V or 0 ~ 5V |
0
~ 20mA or 0 ~ 10mA |
| Maximum
resolution |
0.3mV
(5V/16384) |
0.61µA
(10mA/16384) |
| Accuracy |
±1% |
| Conversion
time |
Conversion
once for each scan |
| Maximum
input signal |
±15V |
±30mA |
| Input
impedance |
63.2Kohms |
250
ohms |
| Isolation
method |
Transformer
(power) and photocouple (signal) isolution |
| Power
input |
24VDC
- 15%/+20%, 2VA max. |
| Dimensions |
Figure
4 |
|
|
Analog output
(AO) modules
|
|
 |
FBs-2DA |
FBs-4DA |
| Number
of output point |
2
points / 14-bit |
4
points / 14-bit |
| Digital
output value |
-8192
~ +8191 or 0 ~ 16383 |
| Output
signal range |
Bipolar |
Voltage:
-10 ~ 10V or -5 ~ 5V, Current: -20 ~ 20mA
or -10 ~ 10mA |
| Unipolar |
Voltage:
0 ~ 10V or 0 ~ 5V, Current: 0~ 20mA or
0 ~ 10mA |
| Maximum
Resolution |
Voltage:
0.3mV (5V/16384), Current: 0.61µA
(10mA/16384) |
| Accuracy |
±1% |
| Conversion
time |
Conversion
once for each scan |
| Maximum
allowable loading |
Voltage:
500ohms ~ 1Mohms : Current: 0ohms ~ 500ohms |
| isolation
method |
Transformer
(Power) and photocouple (signal) isolation |
| Power
input |
24VDC
- 15/+20%, 2VA max |
| Dimensions |
Figure
4 |
|
|
Analog input/output
(AI/O) module
|
|
| Item |
Specification |
| Number
of input/output point |
4
points AI / 14-bit + 2 points AO /
14-bit |
| Analog
input specification |
Same
as FBs-6AD |
| Analog
output specification |
Same
as FBs-2DA / 4DA |
| Dimensions |
Figure
4 |
|
|
Thermocouple
modules
|
|
 |
FBs-TC2 |
FBs-TC6 |
FBs-TC16 |
| Number
of input points |
2
points |
6
points |
16
points |
| Thermocouple
type and temperature measurement range |
J
(-200~1200°C) E (-190~ 1000°C)
K (-190~ 1300°C) T (-190~ 380°C)
R (0~ 1800°C) B (350~ 1800°C)
S (0~ 1700°C) N (-200~ 1000°C)
|
| Temperture
compensation |
Built-in
cold junction compensation
|
| Resolution |
0.1°C |
| Temperature
refresh time |
1
or 2 seconds |
2
or 4 seconds |
3
or 6 seconds |
| Overall
Precision |
±
(1%+1°C) |
| Isolation
method |
Transformer
(power) and photocouple (signal) isolation
(per-channel isolation) |
| Power
input |
24VDC
- 15%/+20%, 2VA max. |
| Dimensions |
Figure
4 |
Figure
1 |
|
|
RTD modules
|
|
 |
FBs-RTD6 |
FBs-RTD16 |
| Number
of input points |
6
points |
16
points |
| RTD
type and temperature measurement range
|
3-wire
RTD sensor (JIS or DIN) Pt-100(-200°C-850°C)
Pt-1000(-200°C - 600°C) |
| Resolution |
0.1°C |
| Temperature
refresh time |
1
or 2 seconds |
2
or 4 seconds |
| Overall
Precision |
±1% |
| Isolation
method |
Transformer
(power) and photocouple (signal) isolation
(no isolation between chanels) |
| Power
input |
24VDC
- 15%/+20%, 2VA max |
| Dimensions |
Figure
4 |
Figure