Fatek

Main Features

Application

Model Specification
- Digital
- Analog
- Communication
- General

Download
Analog input (AI) module

Voltage input
Current input
Number of input point
6 points / 14-bit
Digital input value
-8192 ~ +8191 or 0 ~ 16383
Input signal range Bipolar
-10 ~ 10V or -5 ~ 5V
-20 ~ 20mA or 10 ~ 10mA
Unipolar
0 ~ 10V or 0 ~ 5V
0 ~ 20mA or 0 ~ 10mA
Maximum resolution
0.3mV (5V/16384)
0.61µA (10mA/16384)
Accuracy
±1%
Conversion time
Conversion once for each scan
Maximum input signal
±15V
±30mA
Input impedance
63.2Kohms
250 ohms
Isolation method
Transformer (power) and photocouple (signal) isolution
Power input
24VDC - 15%/+20%, 2VA max.
Dimensions
Figure 4


Analog output (AO) modules

FBs-2DA
FBs-4DA
Number of output point
2 points / 14-bit
4 points / 14-bit
Digital output value
-8192 ~ +8191 or 0 ~ 16383
Output signal range Bipolar Voltage: -10 ~ 10V or -5 ~ 5V, Current: -20 ~ 20mA or -10 ~ 10mA
Unipolar Voltage: 0 ~ 10V or 0 ~ 5V, Current: 0~ 20mA or 0 ~ 10mA
Maximum Resolution Voltage: 0.3mV (5V/16384), Current: 0.61µA (10mA/16384)
Accuracy
±1%
Conversion time
Conversion once for each scan
Maximum allowable loading Voltage: 500ohms ~ 1Mohms : Current: 0ohms ~ 500ohms
isolation method Transformer (Power) and photocouple (signal) isolation
Power input
24VDC - 15/+20%, 2VA max
Dimensions
Figure 4


Analog input/output (AI/O) module

Item
Specification
Number of input/output point
4 points AI / 14-bit + 2 points AO / 14-bit
Analog input specification Same as FBs-6AD
Analog output specification Same as FBs-2DA / 4DA
Dimensions Figure 4


Thermocouple modules

FBs-TC2
FBs-TC6
FBs-TC16
Number of input points
2 points
6 points
16 points
Thermocouple type and temperature measurement range
J (-200~1200°C) E (-190~ 1000°C)
K (-190~ 1300°C) T (-190~ 380°C)
R (0~ 1800°C) B (350~ 1800°C)
S (0~ 1700°C) N (-200~ 1000°C)
Temperture compensation
Built-in cold junction compensation
Resolution
0.1°C
Temperature refresh time
1 or 2 seconds
2 or 4 seconds
3 or 6 seconds
Overall Precision
± (1%+1°C)
Isolation method Transformer (power) and photocouple (signal) isolation (per-channel isolation)
Power input
24VDC - 15%/+20%, 2VA max.
Dimensions
Figure 4
Figure 1


RTD modules

FBs-RTD6
FBs-RTD16
Number of input points
6 points
16 points
RTD type and temperature measurement range 3-wire RTD sensor (JIS or DIN) Pt-100(-200°C-850°C) Pt-1000(-200°C - 600°C)
Resolution
0.1°C
Temperature refresh time
1 or 2 seconds
2 or 4 seconds
Overall Precision
±1%
Isolation method Transformer (power) and photocouple (signal) isolation (no isolation between chanels)
Power input
24VDC - 15%/+20%, 2VA max
Dimensions
Figure 4
Figure 1


home | about us | contact | sitemap 